Shutdown nodes in 8A14, 8A16 and 8A18 - Cooling Leak

Risolto
Parzialmente fuori servizio 30 %
Avviato il 10 mesi faDurato 4 giorni

Colpiti

Cannon Cluster

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

SLURM Scheduler - Cannon

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

Cannon Compute Cluster (Holyoke)

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

Boston Compute Nodes

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

GPU nodes (Holyoke)

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

seas_compute

Parzialmente fuori servizio da 9:45 PM to 4:06 PM

Aggiornamenti
  • Risolto
    Risolto

    Thanks to staff that made multiple datacenter visits, the leak has been addressed and all systems are back up and running.

    This incident has been resolved.

  • Monitorando
    Monitorando

    8a14 and 8a18 are back online, 8a16 is still down

    That includes mweber_gpu and mweber_compute being back up and seas_gpu still partially down

  • Aggiornare
    Aggiornare

    Power and water is shutdown to these racks and the vendor is working to send someone in next working day to investigate. Partition totally down are mweber_compute, mweber_gpu, seas_gpu and seas_compute.

  • Individuato
    Individuato

    Row 8A18 (row 8A rack18) will also be shut down.

  • Verifiche
    Verifiche

    MGHPCC found a leak in 8A14 or 8A16 racks and asked us to shutdown those nodes. We are working with the vendor to fix the issue ASAP.